| Ratings (A) |
30 |
60 |
100 |
160 |
250 |
400 |
600 |
| Source Inputs |
| Rated voltage |
380 V (± 35%) - 400 V - 415 V (± 20%)
|
| Rated frequency |
50 Hz or 60 Hz (± 10%)
|
| Number of phases |
3 ph + N + Earth or 3 ph + N
|
| Operation |
| Permissible overloads |
110% 15 minutes - 150% 2 minutes - 200% 20 ms
|
| Efficiency (linear load & pf = 0.8) |
0.99
|
| Transfer time |
3 ms (typical) / 5ms (maxi)
|
| Environment |
| Air flow (m3/hr) |
350
|
1600
|
2300
|
| Operation |
0°C to 40°C
|
| Storage temperature |
-20°C and +40°C
|
| Noise level (dBA) |
< 60 dB
|
| Standards |
| Manufacturing and safety |
EN 50091-1/ IEC 62040, IEC 60950,
EN 50081-2, EN 50178, EN 50082-2
|
| EMC |
EN 50091-2
|
| Certifications |
TÜV, CE
|
| Dimensions and weight |
| Height x Width (mm) |
1400 x 600 or 1900 x 715
|
1900 x 715
|
| Depth H = 1400 (mm) |
500
|
-
|
| Depth H = 1900 (mm) |
840
|
840
|
| Weight (kg) for H = 1400 mm |
193
|
211
|
-
|
| Weight (kg) for H = 1900 mm |
215
|
225
|
327
|