Active redundancy principles
Upsilon STS™ supplies a number of loads from one of two
independent and redundant sources. It ensures no-break transfer from the
preferred source to the alternate source in either automatic mode (according to
user settings) or manual mode.
Advantages
> secure maintenance
by de-energising a part of the installation for servicing;
> simplified maintenance because servicing
is fast and does not require interrupting power to the load;
> improved power availability and possible
upgrading to higher ratings;
> no risk of fault propagation from one
source to the other.

No-break
transfer
Upsilon STS™ uses the "break before make" technique which
ensures no source overlapping, i.e. the sources are never in parallel during
transfer. This function eliminates any risk of fault propagation between the two
sources.
Upsilon STS™ guarantees transfer in just three milliseconds, i.e. three times
faster than required by IEC international standard 62040.
Upsilon STS™ uses the "break before make" technique which ensures no source
overlapping, i.e. the sources are never in parallel during transfer. This
function eliminates any risk of fault propagation between the two sources.
Upsilon STS™ guarantees transfer in just three milliseconds, i.e. three times
faster than required by IEC international standard 62040.

Standard functions
>
continuous monitoring of the sources (eleven parameters, etc.);
> manual or automatic source transfer and
return with no break in the supply of power;
> rolling-switch function for secure
transfer between desynchronised sources;
> redundant internal STS functions (power
supply, controls, fans);
> isolation switches for maintenance;
> oversized neutral conductor;
> graphic LCD screen and multilingual
display for easy and user-friendly access to the information and setting
screens;
> animated mimic panel for immediate
information on system status;
> two slots available for communication
cards;
> JBus/Modbus (RS232 or RS485) and
dry-contact (six 250 V 2 A relays) communication interfaces.
Optional equipment
>
Top-feed wiring;
> JBus/Modbus, dry-contact (six 250V 2A
relays) communication cards
> PDU power distribution unit (36 x 16 A
circuit breakers, can be installed in the 1900 mm cabinet up to 100 A);
> PMM distribution cabinet
|