The Marshall-Tufflex Steel Trunking Systems are
suitable for the installation of most types of accessories with M3.5 x 60.3mm or
M3.5 x 120.6mm fixing centres using a standard steel flush accessory box with an
internal depth of 35mm.
INSTALLATION
BASE: When used as a skirting system sufficient
clearance should be allowed for between the floor covering and the skirting base
(2mm + floor covering). Secure the trunking base every 750mm with No. 8 screws
by drilling the back of the trunking base. To cut the trunking use a fine tooth
saw and jig. Trunking base and fittings are joined by use of coupling sets. The
coupling sleeve B should be put halfway into the already installed trunking
base. The next section of trunking base can be slid onto the sleeve and fixed
into position. The serrated edged coupler plate is then pushed firmly into the
bottom of the trunking base so that it covers the lower joint A, making a good
bond between consecutive lengths of trunking. Finally the connecting sleeve must
be pushed into position B. Fixing screws, cut edges etc. should be finished in
such a way that no sharp edge can damage the cables inside the trunking.
click to
enlarge

DIVIDING FILLET: This is manufactured from
pre-galvanised steel and is cut to the required length.
COVERS: The covers are provided with pressed
outside grippers which automatically establishes an earth contact when they are
pushed into the trunking base. The length of the covers must be determined so
that the ends are covered by a fitting or accessory. Every cover has to have at
least one pair of side grippers to ensure earth continuity. The length of a cut
cover must be at least 5cm, with the side grippers in the middle. For external
bends and flat angles the appropriate bend covers must be fitted.
ACCESSORY BOXES: Mounting boxes are
available in single and double gang versions and are fixed to the centre rail by
means of a swivel clamp. Boxes can be located at virtually any point on the
length of the trunking with a minimum distance of 50mm between consecutive
accessory boxes. A chosen position can be changed by simply slackening the
fixing screws and sliding the box along the centre rail to a new position.
EARTHING
Each length of trunking and all major fittings and
accessories are fitted with earth connections. The whole of the trunking system
should be installed in accordance with the latest edition of BS7671 (1992) 16th
edition of the IEE Wiring Regulations.
|
click to enlarge |
click to enlarge |
 |
SYSTEM 130
A = 1680mm2 total area 45% SF = 756mm2.
B = 1640mm2 total area 45% SF = 738mm2.
|
 |
SYSTEM 180
A = 2963mm2 total area 45% SF = 1333mm2.
B = 1640mm2 total area 45% SF = 738mm2.
C = 2907mm2 total area 45% SF = 1308mm2. |
 |
SYSTEM 170
A = 2907mm2 total area 45% SF = 1308mm2.
B = 1640mm2 total area 45% SF = 738mm2. |
 |
SYSTEM 190
A = 2963mm2 total area 45% SF = 1333mm2.
B = 1640mm2 total area A 45% SF = 738mm2. |
DESKPOST TECHNICAL
INFORMATION
|
 |
|
DESKPOST
Overall height including cap and base is 670mm. |
|
 |
|
Installation should be in accordance with the latest edition of BS7671
(1992) IEE Wiring Regulations.
Full installation instructions are included within each pack. |
|
DIMENSIONS AND CABLE
CAPACITIES |
|
Click to enlarge |
DESKPOST |
|
 |
A = 1680mm2 total area
45% SF = 756mm2.
B = 1640mm2 total area
45% SF = 738mm2.
C = 7626mm2 total area
45% SF = 3431mm2. |
|
|
|