To contact AURIGA phone 0870 121 9990 fax 0870 121 9991 or email | if you have any problems or feedback please direct them to the webmaster

   home | about | contact | e-catalogue | products | special offers | news | archive | press | site map   

 

Marshall Tufflex Products

Marshal Tufflex Overview

 

Marshall Tufflex Series R Technical Information

 

SERIES R TECHNICAL INFORMATION  

SERIES R

 

Single Gang Accessory Box   Twin Gang Accessory Box
Ref No Depth Standard Pack  

Ref No

Depth Standard Pack
RSSB1 42mm 20   RSSB2 42mm 5

SERIES R TRUNKING CAPACITIES AND DIMENSIONS

SINGLE-CORE PVC-INSULATED CABLES IN TRUNKING

For each cable it is intended to use, obtain the appropriate factor from Table A.

Add all the cable factors so obtained and compare with the factors for trunking given.

The size of trunking which will satisfactorily accommodate the cables is that size having a factor equal to or exceeding the sum of the cable factors.

The number of cables installed should be such that the resulting space factor does not exceed 45%.

Table A

Type of
conductor

Conductor
cross-sectional
area mm2

Factor

Solid

1.5

7.1

2.5

10.2

Stranded

1.5

8.1

2.5

11.4

4

15.2

6

22.9

10

36.3

 

Click image to enlarge

Click image to enlarge

SERIES R 130

A = 1623 sq mm total area 45% space factor = 730 sq mm.

B = 238 sq mm total area 45% space factor = 107 sq mm.

SERIES R 170

A = 2795 sq mm total area 45% space factor = 1259 sq mm.
B = 238 sq mm total area 45% space factor
= 107 sq mm.

SERIES R 130 WITH SEGREGATOR

A = 957 sq mm total area 45% space factor = 431 sq mm.

B = 585 sq mm total area 45% space factor = 263 sq mm.

C = 238 sq mm total area 45% space factor = 107 sq mm.

SERIES R 170 WITH SEGREGATOR

A = 2137 sq mm total area 45% space factor = 961 sq mm.
B = 585 sq mm total area 45% space factor
= 263 sq mm.
C = 238 sq mm total area 45% space factor = 107 sq mm.

SERIES R TECHNICAL INFORMATION

The base is supplied with pre-cut elongated holes at 250mm centres along its length. Fasten the base with No. 8 round head screws and washers. Avoid over tightening to permit thermal movement. All base joints should have a 3mm gap (min) to allow for expansion left between consecutive lengths which are covered by the coupler. Fabricated internal/external bends are installed as per the base. The internal segregator and dividing fillet both clip within the base.

ACCESSORY BOXES

These are clipped to the D rail and secured by means of the accessory mounting screws for the 1 gang box or the independent fixing screws on the 2 gang box. This offers very secure location of the boxes.

 

© AURIGA (europe) PLC 2004, E&OE | last updated 20-09-06 14:19 | Privacy Statement | Site Map | Help