Bench Trunking utilises the
successful Sterling compatible surface and flush clip-on accessories and can be
subdivided with the use of Clip-in Divider Fillets. In both PVC-U and aluminium
the option of material is available whatever the application.
MOUNTING
Secure the base in one plane only
every 500mm by drilling alternate 6mm holes either side of the divider nib and
fasten using No. 8 round head screws and washers. Do not over tighten to permit
thermal movement and avoid distortion. See Material Data page 203 for thermal
properties. Washers are not required on Aluminium Base.
click to
enlarge

JOINTS
PVC-U base should be joined using
a connector with 3mm of movement available between consecutive lengths of base.
The lid part of the connector also has 10mm overlap on each side to facilitate
thermal movement of the trunking due to change in temperature.
Aluminium base the consecutive lengths are aligned and butt jointed together.
FITTINGS
Dividing fillets are snapped on to
the internal nibs in the base. Accessories and boxes clip direct into the
trunking base and the lid cut to length and pressed into position. The lid
connector is now aligned with the base connector (PVC-U only) and the end caps
secured using a solvent adhesive MSC3 (PVC-U only) and the retaining screws for
use with aluminium.
EARTHING (ALUMINIUM)
Covers, base and metallic fittings
are to be cleaned of protective coating and earth bonded. Incoming earth
connectors are made using the LBT1 Bonding Assembly installed in the earth
channel of the base. In final ring or radial 32A circuits the bonding strap LBS1
may be used in the earth channel for bonding lengths of trunking. The base,
cover and end caps should be bonded using the Bonding Strap LBS2.
LID REMOVAL PVC
This is best attended to at an
accessory, end cap or coupler to avoid damage to the lid. Remove the fitting and
applying light pressure under the lid peel off a small section (300mm) at a
time.
LID REMOVAL ALUMINIUM
Remove accessory face plate cover
and then gently ease lid from the base taking care to avoid damage.
DIMENSIONS AND CABLE CAPACITIES
 |
A = 1285 sq mm total
area 45% space factor = 578 sq mm.
B = 2138 sq mm total area 45%
space factor = 962 sq mm. |
The installation should be in
accordance with the latest edition of BS7671 (1992) Wiring Regulations. |