STERLING ELEGANCE ALUMINIUM
The single system compartment aluminium trunking
from Marshall-Tufflex is available with an optional Busbar System from the
successful Sterling range. A full range of bonding straps and connectors are
available.
POSITIONING
When used as a skirting system sufficient
clearance should be allowed for between the floor covering and the trunking with
due allowance for wiring accessories.
INSTALLATION
Secure the trunking base every 750mm with no.8
round head screws, utilising the grooves in the base to facilitate the drilling
of 6mm clearance holes. Use a fine tooth blade (32/36tpi) or preferably a
circular saw with a 350mm diameter fine tungsten tipped blade (96/108tpi) for
cutting the aluminium trunking. This will produce an edge requiring minimal
deburring.
JOINTS
Consecutive lengths are butt jointed together. The
covers are cut square and staggered from the carrier base.
FOR ANGLES AND TEES
Remove the covers from the fittings and store in a
safe place to avoid damage. Align and secure within 75mm of the edge of the
fitting as previously described.
ACCESSORY BOXES
Remove the appropriate KO or drill the box and
feed the cables into the box and clip into the desired location. All Flush
Accessories must have front fixing screws visible to enable removal of the
cover.
COVER REMOVAL
The cover has been designed to remain captive
during normal conditions and minor undulations to the base. To remove cover
release accessory screws, using tool LRT1 – insert between cover and base,
lifting up to release the cover whilst working along the length. On no account
use a screwdriver or other metallic object as this can distort or damage the
finish to the cover.
click to
enlarge

BUSBAR ASSEMBLY
Upgrades the trunking to a 63A Busbar distribution
system. Comprises: carrier support, carrier clip, Busbar rails, protective
cover, cover screws. Requires Busbar Adaptor (LAC1) to position Busbar Assembly
within the trunking base. For Busbar fittings, accessories and installation
please refer to relevant sections.
click to
enlarge

EARTHING
Covers, base and metallic fittings are to be
cleaned of protective coating and earth bonded. Incoming earth connectors are
made using the LBT1 bonding assembly installed in the earth channel of the base.
For circuits protected by a device greater than 32A, the connector LBT2 is
required to bond two lengths of LTB base together. In final ring or radial 32A
circuits the bonding strap LBS1 may be used in the earth channel for bonding
lengths of trunking. Covers, end caps and metallic fittings should be bonded
using the bonding strap LBS2 onto the earth upstand.
click to
enlarge

Bonding Terminal (LBT1)
Terminating the incoming earth to the trunking
base. Cable capacity 16mm2.
Bonding Connector (LBT2)
Base earth continuity link for 63A Busbar.
Bonding Strap (LBS1) 4.0mm2
Base earth continuity strap for 32A system.
Bonding Strap (LBS2) 1.5mm2
Base to cover/end cap earth continuity link.
The installation should be in accordance with the
latest edition of BS7671 (1992) Wiring Regulations. |