HELLERMANNTYTON Networks Sciences approved Category 6 UTP cables suitable for campus, riser and horizontal Installation. Compatible with all known connection systems according to EN50173(2000). Applicable standards: ISO/IEC 11801 - 2nd Edition, EN 50173(2000); PrEN 50288-6-1 Fire Propagation Test : UL 1581 VW1 and IEC 332.1 |
 |
|
Product range |
| Description |
Length |
Part No. |
Stk Code |
|
PVC sheath |
305m box |
CA085 |
187-32C/GRY |
|
LSZH sheath |
305m box |
CA076 |
187-33D/VIO |
|
|
|
| Cable Properties |
| Minimum installation bend radius |
8 x Dia |
| Minimum Installed bend radius |
4 x Dia |
| Maximum installation tension |
100N |
| Maximum installed tension |
Zero |
| Installation temperature range (Installed) |
0 to 50ºC |
| Operating temperature range |
-20 to 60ºC |
|
|
Cable construction |
| Conductor |
Bare Copper wire |
| Insulator material |
Polyethylene |
| Number of twisted pairs |
4 |
| Spline material |
PVC or OHLS |
| Sheath material |
PVC or OHLS |
| Outside diameter of conductor |
0.575 mm |
| Outside diameter of insulation |
1.00 mm |
| Outside diameter of sheath |
6.40 mm |
| Weight PVC (OHLS) |
39.1(41.2) kg/km |
| Sheath printing (up to 24 characters) |
Batch No. & Metre marking |
|
|
Electrical characteristics @ 20°C |
|
Characteristic impedance (1-100MHz) |
100 ± 15Ω |
|
Characteristic impedance (100-250MHz) |
100 ± 18Ω |
|
DC Conductor Loop Resistance |
25Ω/100m |
|
Max. Resistance unbalance |
<2% |
|
Nominal Velocity of Propagation |
66% |
|
Nominal Capacitance |
50pF/m |
|
Max. Capacitance unbalance |
1600pF/km |
|
Insulation Resistance (500V) |
>2000 MΩ.km |
|
|
Packaging |
|
Packaging type |
‘Reelex’ |
|
Length per box |
305 m |
|
Box Dimensions (wdh) |
400 x 400 x 230mm |
|
Weight (approx.) |
13kg |
|
|
|